Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Sprinkler - Final
Permit Number - T18FC00366
Inspection Description - COT - FCON - Sprinkler - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2019 | COT - FCON - Sprinkler - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - Tested the fire pump. The fire pump passed the inspection, however, the signals could not be verifyed to the fire alarm system so the fire pump is locked out until the signals can be confirmed. Need to verify that the fire pump, water flow and tamper signals are reportting off site prior to approving a TCO for fixturing of the building. |