Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00360
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2018 | FIRE - ALARM FINAL | Approved | ||
11/21/2018 | FIRE - ALARM FINAL | Partial Approval | Alarm final inspection. PA. Missing items below. -breaker lockouts -72/ROC required at final -PS 5 - LP 1, circuit not working. need to retest to verify this circuit working. -add pull station at fuel kisosk per plans. -FACP sign @ door. -GC for TI advised to mount FDC sign. Min 6" letters and min 6' AFF. |
|
11/14/2018 | FIRE - ALARM FINAL | Denied | Alarm was not ready for final. Inspection #1. Contractor alarm and fire final can be approved once alarm is functional. |