Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2018 | FIRE - ALARM FINAL | Approved | ||
| 07/31/2018 | FIRE - ALARM FINAL | Partial Approval | Needs the disconnecting means labeled in the FACP Red lock out required on the main breaker Manual station near room 218 needs to be lowered to 42-48 operable parts Trouble shoot !115,231 and 114 Still need to confirm the sounder operation in the 100 wing. Confirmed signals to central station and tested all the other devices. |