Permit: T18FC00198

Parcel: 117050590


Addresses:

415 N 6TH AV

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
05/25/2018 FIRE SPKLR - FINAL Approved
05/18/2018 FIRE SPKLR - FINAL Partial Approval -adding some heads in NW room. also adding a head to cover under the stairs, East side.
-flowed inspectors test, main drain test.
-only needs a final walk to inspect the heads that were added and spare head box mounted.
-also need knox fdc plugs.