Permit: T18FC00127

Parcel: 11105262A

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
07/17/2018 FIRE SPKLR - OH PIPING & HYDRO Approved
06/05/2018 FIRE SPKLR - OH PIPING & HYDRO Approved OH approved however permission not granted to cover ceiling. Need either head moved or central vaccuum pvc moved head is less than 4 inches away. There was also duct work touching a few sprinklers that need to be 4 inches or greater. Also insulation needs to be removed from sprinkler heads.