Permit: T18FC00089

Parcel: 123020830


Addresses:

2540 E GRANT RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
06/14/2018 FIRE SPKLR - FINAL Approved
05/15/2018 FIRE SPKLR - FINAL Partial Approval 1) Missing head in riser room.
2) Sprink system needs to be elec supervised.
3) Annual sprink inspection required. Provide report.
4) 5yr internal check valve inspection. Provide report.