Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2018 | FIRE - ALARM FINAL | Approved | ||
| 02/28/2018 | FIRE - ALARM FINAL | Partial Approval | Flow switch was 55 seconds. Manual pull and smoke detector ok Needs 12v 18ah batteries Needs a re lock out on the breaker Correct the time and date stamp Change the program so that the siren does not sound on a fire alarm Program the ground fault to show as a ground fault not the zone in trouble |