Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INSP - OPERATIONAL PERMIT
Permit Number - T18FC00028
Inspection Description - FIRE INSP - OPERATIONAL PERMIT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2018 | FIRE INSP - OPERATIONAL PERMIT | Approved | ||
05/17/2018 | FIRE INSP - OPERATIONAL PERMIT | Denied | -all horn/strobes do not communicate with each other. -high alarm is a supervisory. needs to be a general alarm. |
|
04/25/2018 | FIRE INSP - OPERATIONAL PERMIT | Denied | DENIED. Not ready. 1) Did not have equipment to test CO2 alarm. 2) Still needs full CO2 alarm acceptance test. 3) Will mount 704 diamonds to SW exterior door and NE exterior door. 4) Reinspection fee added to this permit. Must be paid prior to next inspection. 5) Mount "911 emergency" card next to central unit. 6) You shall pretest alarm prior to next inspection. |
|
04/12/2018 | FIRE INSP - OPERATIONAL PERMIT | Denied | DENIED, not ready. Nobody on site to test. No message. No appointment. Tyco did no answer phone or return my messages. Need the following: 1) Schedule acceptance test with myself. John Vincent 5203495581. 2) Need as-builts prior to full final/approval. Devices not installed in locations per plans. Need to add sequence of operations to plans. 3) Post 704 diamonds on exterior west and east doors. 4) Label and lockout circuit breaker. 5) Reinspection fee added to this permit. Must be paid prior to next inspection. |