Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T18DV08151
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | Met With TFD, ADOT and property manager. Found new walls added, new toilet with sump ejection system and new Pex lines for water.There is an exhaust system installed in the bathroom. One evap cooler is sitting on the interior floor and one routed outside. Found no heat present. Found new electric and lights. New M/C cables ran and not supported correctly. There is a new wall running the entire length of the floor from north to south. A suite is occupied without egress directly to the exterior. They must pass through the larger space. |