Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 11/01/2018 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
EMERGENCY CALL OUT BY TFD" THERE WAS A CONTENTS FIRE IN A MASONRY SHED, POSSIBLE BEING USED AS A DWELLING. THE SHED HAS CEILING DRYWALL DAMAGE AND BROKEN WINDOW. THE SHED HAS INTERIOR WIRING TO THE COOLER WITH HEAT DAMAGE, THE SHED HAS A 60 AMP PANEL WITH NO GROUNDING SYSTEM, NO DEAD FRONT, GROUNDS AND NEUTRALS ARE NOT SEPARATED. THIS PANEL WAS BEING FEED BY THE REAR DWELLINGS MAIN DISCONNECT. THE MAIN DISCONNECT HAS MULTIPLE CODE VIOLATIONS, NEW MULTIPLE EMT RUNS TO UNKNOWN LOCATIONS, NO DEAD FRONT, MULTIPLE CONDUCTORS ON A TERMINAL LUG OF THE BREAKER, MISSED MATCHED BREAKERS. TEP DID DISCONNECT POWER, PERMIT REQUIRED FOR RECONNECT. REAR DWELLING WAS CONDEMNED |