Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T18DV06493

Parcel: 124090850


Addresses:

1750 E 9TH ST


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T18DV06493

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2018 INSP - INITIAL CODE ENFORCMENT Approved Tenanmt complained of shocks from receptacles. We have grounded receptacles on non-grounded circuits. Ground wires have been connected to the non-grounded boxes with sheet metal screws. The sub panel has two wire circuits with no ground wires. There are no GFCI's in the circuits. Sub panel not labeded.