Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T18DV06493
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | Tenanmt complained of shocks from receptacles. We have grounded receptacles on non-grounded circuits. Ground wires have been connected to the non-grounded boxes with sheet metal screws. The sub panel has two wire circuits with no ground wires. There are no GFCI's in the circuits. Sub panel not labeded. |