Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T18DV06308
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | ONSITE INSPECTION PER TUCSON POLICE REQUEST, THE PARK'S SERVICE IS 600 AMPS WITH THREE 200 AMP PANELS. THE PARK FEEDERS ARE OVER HEAD, THE POWER POLE LOCATED IN SPACE 39 HAS BROKE IN HALF, THE STRAIN OF THE BREAK HAS SHIFTED THE RISER AND CAUSING THE EQUIPMENT DISCONNECT TO TWIST OFF THE BACKER BOARD. THE OVER HEAD FEEDERS ARE SUPPORTING THE BROKEN POLE. THE CITY ORDER IS TO HAVE A LICENSE ELECTRICAL CONTRACTOR TO DISCONNECT THE FEEDERS TO THE POLE TODAY. MANAGEMENT DID HIRE COMMONWEALTH ELECTRICAL COMPANY. LATER THAT DAY I MET THE CONTRACTOR ONSITE AND HE DID REMOVE THE FEEDERS FROM THE BROKE POWER POLE AND SECURE THEM TO THE ADJACENT POWER POLE. UNIT 39 TENANT WAS ISSUED AN ORDER TO VACANT NOTICE DUE TO POWER DISCONNECT. THE POWER POLE LOCATED ON THE VACANT SPACE ADJACENT TO THE MAIN SERVICE HAS MOVEMENT AND IS NOT PROPERLY SUPPORTED. THERE ARE OTHER CODE VIOLATIONS ON THE PROPERTY CONSISTING OF OVER 30 MOBILE HOMES, I ADVISED MANAGEMENT THAT I WOULD NEED ACCESS TO EACH SPACE TO CONDUCT INSPECTIONS OF THE EQUIPMENT DISCONNECTS. |