Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 07/16/2018 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
Received call from office that cooler not working. Arrived and maintenance on site. Did check the cooler in the rear of the apartment and the water was not coming out of the spider. The maintenance man put the hose on the spider and the water was coming out. Then the pump was working and no water was coming out of the spider when conected. The pump was than checked and was plugged at the base of the pump. The pump was cleaned and than connected and was working. The water was coming out of the spider. At this time the case will be closed. Violation Abated, Close Case. RV. |