Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T18DV03261
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | Permit #T18CM05498 has been secured, inspected and passed. At this time Code Enforcement does not have any further jurisdiction or authority. | |
09/07/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | Permit T18CM05498 Issued. Observe as per Building Official | |
07/13/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | Met with the owners rep and contractor. Found possible discrepincies in electric, mechanical and plumbing, Structrural possible at new sky light. Found new recessed cans, and ceiling fans. The subpanel has new breakers and labeling is not correct. there appears in the ceiling multiple junction boxes. The new split units. Found a exhaust inside of the shower. found inconsistencies in the nailing and supports on the porch. | |
06/20/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | Met with the owners rep. Owner is out of country. Found porch has been modified and three new A/C's have been added. Other signs of work done. Rep will get ahold of the owner to set up an apointment to view the interior. | |
06/14/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | No Answer at door. Posted "Stop Work" and NOV |