06/26/2018 INSP - INITIAL CODE ENFORCMENT Approved PANEL WAS REMOVED ON VACANT LOT..ALSO CONNECTIONS AT THE MAIN DISCONNECT. CLOSE CASE
05/31/2018 INSP - INITIAL CODE ENFORCMENT Approved ON SITE TRAINING
05/31/2018 INSP - INITIAL CODE ENFORCMENT Approved THERE ARE HAZARDOUS ELECTRICAL ON THE VACANT LOT, MULTIPLE JUNCTION BOX HAVE BEEN INSTALLED FOR THE PURPOSE OF A PEDDLER BUSINESS. THE FEEDERS RUN UNDERGROUND FROM THE BUILDING LOCATED AT 4782 S 12TH AVE THRU TWO VACANT LOTS AND COME UP ABOVE GROUND TO A HAZARDOUS PANEL BEING SUPPORTED BY TWO PVC CONDUITS AND A STICK, THIS PANEL NO DEAD FRONT, UNUSED OPENING, EXPOSED ENERGIZED CONDUCTORS AND NO GROUNDING SYSTEM. THE POWER CONTINUES FROM THIS POINT UNDER TO THE MULTIPLE JUNCTION BOXES WHICH IS BEING USED BY THE PEDDLER BUSINESS.

ALL EQUIPMENT HAS BEEN IDENTIFIED WITH THE PROPERTY OWNER. THE CIRCUIT AT THE MAIN DISCONNECT WAS SHUT OFF ON SITE.

THE MAIN DISCONNECT HAS A MISSING DEAD FRONT AND TWO CORD CONNECTED TO BREAKERS AS PERMANENT WIRING.