Case: T18DV02745

Parcel: 115071230


Addresses:

27 W ELM ST


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T18DV02745

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2018 INSP - INITIAL CODE ENFORCMENT Approved Called to the site to check the ductwork, furrdowns, the electrical wiring on the wall the was removed from the framing due to not connected to the furrdown. Has no cooling and the cooler was taken off the roof and being placed in the window in the living room. Has loose light fixtures on the exterior that have been added the not installed properly. Was lacking smoke detectors and found the where the dryer has been place in the kitchen area and has the flex duct going out the window in the rear of the house and temporary connected with wire to keep in place. RV.
05/15/2018 INSP - INITIAL CODE ENFORCMENT Approved AIRDUCT SYSTEM RUSTED THOUGHOUT, WOOD FRAME HOLDING UP AIR DUCT SYSTEM IS DAMAGED BY WATER AND TERMIT. PARTS OF WOOD FRAMING ARE CRACKED THROUGH, AC COOLING UNIT ADDED W/OUT PERMITS, EXPOSED ELECTRICAL WIRES, HOLE IN WALL, FAN IN KITCHEN HAS A HOLE AT THE BASE OF THE CEILING FAN., EXTERIOR LIGHT FIXTURE ON OUTSIDE OF RENTAL HAVE EXPOSED WIRING. CONTACTED OWNER AND WALKED HIM THOUGH THE ENTIRE RENTAL AND POINTED OUT EACH ITEM THAT NEEDED TO BE FIXED UNDER PERMIT WITH A CONTRACTOR. FU IN 5 DAYS