Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CALL OUT BY TFD: THERE IS FIRE DAMAGE TO THE 3050 SIDE ROOF RAFTERS AND INTERIOR FRAMING MEMBERS WERE DAMAGED BY FIRE. THERE IS A ROOF CUT OUT IN THE AREA OF THE BEDROOM/BATHROOM /HALLWAY. THERE IS INTERIOR DAMAGE BY FIRE TO ELECTRICAL WIRING SYSTEM, DRYWALL IN THE SAME LOCATION.THERE IS A INSPECTION HOLE IN THE LIVING ROOM CEILING AREA. POWER WAS DISCONNECT BY TEP TO BOTH MAIN DISCONNECTS. BOTH GAS METERS WERE SECURED AND PINNED BY SWG. THE UNIT 3052 HAS HEAVY SMOKE NO PHYSICAL DAMAGE FROM THE FIRE. THE DWELLING WAS CONDEMNED. THE FOLLOW ARE CODE VIOLATIONS NOTICED DURING INSPECTION. THE DUPLEX WAS CONVERTER INTO A SFR WITHOUT APPROVALS. THERE IS AN ARCH OPENING 5 X 7 IN BETWEEN THE UNITS. UNIT 3050 HAS HAD KITCHEN REMOVED AND AREA NOT HAS BEDROOM. THERE ARE MULTIPLE WINDOWS WHICH HAVE BEEN BLOCK IN AND A DOOR OPENING. BOTH DISCONNECTS HAVE MISSING DEAD FRONTS. UNAPPROVED WIRING METHODS. THERE IS A CORD TAPPED INTO MAIN BREAKER SUPPLYING POWER TO DRYER OUTLET. THERE IS FLEX TYPE CONDUIT RUNNING TO NEW ROOF MOUNTED HVAC UNIT. INSTALL OF WATER HEATER NOT PERMITTED ALSO UNAPPROVED WIRING METHODS TO THE UNIT. THE UNIT SIDE 3052 HAS NEW J BOXES WITH RECEPTACLES IN KITCHEN COUNTER NO GFCI, ALSO NEW BOXES WITH RECEPTACLE IN HALLWAY FOR WASHER. NEW DRYWALL INSTALLED IN KITCHEN. |