Permit: T18CM10063

Parcel: 113101390


Addresses:

1646 E COPPER ST

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/12/2019 ELECTRIC - FINAL Not ready for Inspection Unable to access for inspection. Left voicemail with contact on file.
08/12/2019 ELECTRIC - FINAL Approved
08/08/2019 ELECTRIC - FINAL Not ready for Inspection Arrived at site at 2:15 PM. Rang bell and knocked on door. Gate locked. No access to garage. Please recall with access information.
08/06/2019 ELECTRIC - FINAL Denied 1. All outlets in the garage/storage area, must be gfi protected.
2. Sub panel neutral and ground bars must be separated from each other. This will require removing the connecting bar that runs behind the buss bar. Then the ground bar must be connected to the panel jacket with the green ground screw and s bar attachment to the ground bar.