Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T18CM09936
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2019 | FRAMING | Approved | ||
03/19/2019 | FRAMING | Denied | Need to fire block at garage door chase horizontal openings Cut tar paper back away from B vent at water heater Support 4 gang switch in den Remove H25 clips on 2 point bearing trusses on east wall of den Move pex in den ceiling 12” from can lights Missing outlet on west kitchen wall Missing anchor bolt nuts at various locations throughout Roof truss north of hallway entry in living room correct bearing point as needed Shim bearing point of truss south of garage hallway in living room Support 4 gang switch in living room Need to put boca plate over 2” abs over bore in top plate in master bathroom No pressure on potable water |