Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T18CM09869
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2018 | PLUMBING - INTERMEDIATE | Approved | ||
| 12/27/2018 | PLUMBING - INTERMEDIATE | Correction Required | No black iron gas pipe allowed to be buried. Open ditch from water heater to gas meter. Replace black iron pipe with approved coated pipe for direct burial. This install needs to be tested and inspected. Water heater to be 3” above slab or dirt on an approved pad. Connector lines to be 6” from the vent. Gas B vent to be 1” from facia as the bracket should provide. |
|
| 12/24/2018 | PLUMBING - INTERMEDIATE | Not ready for Inspection | No one onsite, Units not addressed or labeled, Rehab project Units not occupied. |