Permit: T18CM09869

Parcel: 11106175A


Addresses:

3727 E GLENN ST #J


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T18CM09869

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2018 PLUMBING - INTERMEDIATE Approved
12/27/2018 PLUMBING - INTERMEDIATE Correction Required No black iron gas pipe allowed to be buried. Open ditch from water heater to gas meter. Replace black iron pipe with approved coated pipe for direct burial. This install needs to be tested and inspected.
Water heater to be 3” above slab or dirt on an approved pad.
Connector lines to be 6” from the vent.
Gas B vent to be 1” from facia as the bracket should provide.
12/24/2018 PLUMBING - INTERMEDIATE Not ready for Inspection No one onsite, Units not addressed or labeled, Rehab project Units not occupied.