Permit: T18CM09837

Parcel: 138020120

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/30/2019 MECHANICAL - FINAL Approved
09/19/2019 MECHANICAL - FINAL Denied 1- Shall replace the flex connector to the Gas pack on roof. The nomenclature tag has been painted and can not verify size, length and BTU load. 2- Shall provide a flashing for the condensate line roof penetration.
09/05/2019 MECHANICAL - FINAL Denied 1- Shall extend and terminate the condensate drain a minimum of 6 inches above sub grade.
2- Condensate drain has back pitch and shall be protected with approved coating.
Note; The owner has allowed the tenants move in without the building final approval.
08/30/2019 MECHANICAL - FINAL Denied 1- No one home at time of inspection request.
07/24/2019 MECHANICAL - FINAL Not ready for Inspection previous corrections were not addressed at all. Another failed inspection will result in a reinspection fee.
07/23/2019 MECHANICAL - FINAL Partial Approval smoke alarm outside new sleeping area needs to be carbon monoxide as well. Kitchen either needs exhaust fan or hood installed. Water heater either needs disconnect or lock out tag out at panel. T&P piping needs to be installed.