Permit: T18CM09837

Parcel: 138020120

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/30/2019 PLUMBING - FINAL Approved
09/19/2019 PLUMBING - FINAL Denied 1- Overhead domestic water supply line to the main bathroom shall be insulated due to cold water turns to hot because it is located in attic space. 2- Shall cap off the water heater drain pan outlet
09/05/2019 PLUMBING - FINAL Denied 1- Water heater T & P drain not provided and shall extend and terminate into the drip pan and cap off the pan drain outlet.
2- Shall provide water hammer arrestors for the clothes washer water supply outlets.
3- The flex connector for the Range can not pass thru the wall of the cabinet. This must be hard piped thru the case work.
4- Shall paint the sanitary vent thru roof with. Laytex base paint.
5- The lavatory cold water supply comes out hot for awhile then turns cold after running due to no insulation on piping.
6- Shall remove the painted flex connector at AC Gas pack unit for proper size verification
08/30/2019 PLUMBING - FINAL Denied 1- No one home at time of inspection request.
07/24/2019 PLUMBING - FINAL Not ready for Inspection previous corrections were not addressed at all. Another failed inspection will result in a reinspection fee.
07/23/2019 PLUMBING - FINAL Partial Approval smoke alarm outside new sleeping area needs to be carbon monoxide as well. Kitchen either needs exhaust fan or hood installed. Water heater either needs disconnect or lock out tag out at panel. T&P piping needs to be installed.
07/15/2019 PLUMBING - FINAL Not ready for Inspection no access, no one home, no key in lock box.
03/26/2019 PLUMBING - FINAL Not ready for Inspection currently at intermediate stage not at finals