Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2019 | ELECTRIC - FINAL | Approved | ||
| 09/05/2019 | ELECTRIC - FINAL | Denied | 1- Shall secure the Ufer ground conductor to the wall under the service panel. 2- Shall provide a lock out tag out clip for the water heater dedicated circuit breaker. |
|
| 08/30/2019 | ELECTRIC - FINAL | Denied | 1- No one home at time of inspection request. | |
| 07/24/2019 | ELECTRIC - FINAL | Not ready for Inspection | previous corrections were not addressed at all. Another failed inspection will result in a reinspection fee. | |
| 07/23/2019 | ELECTRIC - FINAL | Partial Approval | smoke alarm outside new sleeping area needs to be carbon monoxide as well. Kitchen either needs exhaust fan or hood installed. Water heater either needs disconnect or lock out tag out at panel. T&P piping needs to be installed. | |
| 07/15/2019 | ELECTRIC - FINAL | Not ready for Inspection | no access, no one home, no key in lock box. | |
| 02/28/2019 | ELECTRIC - FINAL | Not ready for Inspection | need to pass residential intermediate prior to this inspection. |