Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2019 | MECHANICAL - FINAL | Approved | REVIEW OF AIR BALANCE REPORT COMPLETED | |
| 04/05/2019 | MECHANICAL - FINAL | Partial Approval | Need to submit Air Balance report to City of Tucson. | |
| 03/27/2019 | MECHANICAL - FINAL | Denied | Install bonding jumper across furnace plenum vibration collar. A/c unit is over fused per spec tag. label all breakers |
|
| 03/25/2019 | MECHANICAL - FINAL | Not ready for Inspection | currently at intermediate stage not final | |
| 12/21/2018 | MECHANICAL - FINAL | Prior to Final Inspectn | AIR BALANCE REPORT REQUIRED |