Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2019 | BUILDING - FINAL | Partial Approval | approved by inspector, but need water report-cb | |
| 04/18/2019 | BUILDING - FINAL | Denied | 1- Shall locate the lavatory 15 inches from side wall to center of faucet and drain minimum. 2- Shall locate the toilet paper dispenser as per section 604.7 A117.7.1 3- Shall provide a trap guard on exterior shower drain. 4- Shall provide a approved shower diverted control chain or handle on exterior shower valve. 5- Shall provide accessibility signage at toilet room. |