Permit: T18CM09733

Parcel: 10821323A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/09/2019 BUILDING - FINAL Approved
04/05/2019 BUILDING - FINAL Denied 1- Shall provide a platform to access the water heater located in the ceiling.
2- Shall provide a expansion tank for the water heater.
3- Shall provide a vacuum relief valve for the water heater located on the cold supply.
4- Shall label all circuit breakers in service panel.
5- Shall seal the water supply penetration at exterior wall.
6- Shall complete stucco around windows.
7- Shall provide temperature mixing valves at men’s and women’s lavatories.
8- Shall provide accessible signage for men’s and women’s restrooms.
9- Shall locate the towel dispenser height as per ANSI standards.
10- Shall provide a hose bib vacuum breaker at hose bib.
11- Shall provide address on building.
12- Shall provide protection wrap on lavatories waste and supply lines.
13- Shall provide toilet paper dispenser and locate per ANSI standards.
14- Shall complete insulation above ceiling.