Permit: T18CM09617

Parcel: 11301146Z


Addresses:

3699 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T18CM09617

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2019 MECHANICAL - ABOVE CEILING Approved
05/03/2019 MECHANICAL - ABOVE CEILING Not ready for Inspection Work incomplete at this time. Note: Observed exhaust duct from adjacent suite( that was formerly combined with this suite) through demising wall. Plan does not specify fire rating of demising wall. Builder will submit RFI to clarify how this is to be dealt with, and submit for revision. Will have approved revision on site for this inspection