Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T18CM09617
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2019 | MECHANICAL - ABOVE CEILING | Approved | ||
05/03/2019 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | Work incomplete at this time. Note: Observed exhaust duct from adjacent suite( that was formerly combined with this suite) through demising wall. Plan does not specify fire rating of demising wall. Builder will submit RFI to clarify how this is to be dealt with, and submit for revision. Will have approved revision on site for this inspection |