Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2019 | ELECTRIC - FINAL | Approved | ||
| 01/11/2019 | ELECTRIC - FINAL | Not ready for Inspection | All nr's are incomplete or need corrections. 1. Repair kitchen sink drain leak. 2. Install outlet north of kitchen sink and make both North counter outlets GFI protected and fix bath GFI. 3. Need gas and water Bonds to panel. 4. Confirm that gas line is run under additional slab and do a pressure test. 5. Move to smoke detectors to high points in rooms with pitched ceiling's. 6. Paint conduit support blocks on roof. 7. I need arc fault breaker's where required by code. 8. Raves dishwasher drain to counter bottom. 9. I need licensed electrician to do the whole house system evaluation and report on letter head. 10. Replace PVC at front water riser. 11. Seal flu hole in hot water heater cabinet lid from water penetration. |
|
| 01/04/2019 | ELECTRIC - FINAL | Correction Required | No plans nor permit on site. |