Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T18CM09551
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2019 | SHEET ROCK NAILING | Approved | ||
05/21/2019 | SHEET ROCK NAILING | Partial Approval | Unit #6 ok only | |
05/07/2019 | SHEET ROCK NAILING | Partial Approval | Upstairs rooms 7-12 and 103 To include 5/8” sheet rock fire separations between units on walls | |
04/19/2019 | SHEET ROCK NAILING | Partial Approval | units #1, 32, 2, 4 and downstairs hallway. Double 1/2" on ceilings | |
04/12/2019 | SHEET ROCK NAILING | Partial Approval | OK to proceed second layer ceilings. | |
04/10/2019 | SHEET ROCK NAILING | Denied | Provide RFI for all ceiling fire separations prior to next inspection | |
04/02/2019 | SHEET ROCK NAILING | Partial Approval | units inspected were 5 and 3. Need an RFI or an email from the design team stating what is being done on the fire walls and ceilings meets a one hour rating necessary between units. Currently there is half inch type C on walls and ceilings which is raising Questions. | |
04/01/2019 | SHEET ROCK NAILING | Partial Approval | Units 3 & 5 pending Friday for fire separation at ceilings |