Inspection History Details
Inspection Status: Passed
Inspection History: COT - LCBU - Framing
Permit Number - T18CM09411
Inspection Description - COT - LCBU - Framing
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2019 | COT - LCBU - Framing | ESTEVENS | Approved | Entered by DMERANZ1 - |
12/11/2019 | COT - LCBU - Framing | JCLAXTON | Denied | Entered by DMERANZ1 - Replace stud at patio wall west side that is in 2 pieces, plans call for full height stud. Kitchen where exhaust duct goes thru top plate need to put fha plates across both plates. Recall prior to placing osb on walls. |
12/06/2019 | COT - LCBU - Framing | TVALENCIA | Denied | Entered by DMERANZ1 - 1- Shall seal all electric conductors that penetrate the top plates. 2- Shall provide (3) sided blocking on the second floor forced air vents. 3- Shall provide a clean out at the 3 inch soil stack. 4- Shall secure the horizontal pex water lines every 32 inches. |