Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM09287

Parcel: 116293190


Addresses:

1080 S CASTAR DR

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/20/2019 PLUMBING - INTERMEDIATE Approved
02/19/2019 PLUMBING - INTERMEDIATE Denied 1- Clothes washer trap arm does not have a minimum trap arm distance.
2- horizontal vent for the gray water clothes washer and the hallway bathroom water closet shall be located a minimum of 6 inches above the flood level rim of fixture.
3- Shall secure the closet rings to the floor.
4- Re-test the DWV system.