Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2019 | FIRE - FINAL | Approved | -will post all "not an exit" signs. -will remove exit sign from kitchen door. -will post decals "these doors to remain unlocked..." over main exit and main exit security door. -knox box x 2 (front gate and west gate) -gate locks to be mounted on street side of gates. |
|
| 11/19/2019 | FIRE - FINAL | Partial Approval | -need an exiting plan submitted by architect showing which doors are to be used as exits. -sliding barn doors inbetween rooms cannot be used in the path of egress for exiting. -remove slidebolts from exit doors. -remove pad lock hardware from exit doors. -post not an exit on doors that will not be considered exits. -12" minimum address numbers on bldg, east side. -determine your plan for front gates. FD pad lock, knox box, etc... -mount extinguishers. |