Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T18CM09065

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2019 REINFORCED MASONRY PRE-GROUT Approved
04/12/2019 REINFORCED MASONRY PRE-GROUT Partial Approval only pending special inspection report on final lift
04/11/2019 REINFORCED MASONRY PRE-GROUT Partial Approval west exterior wall and north west corner of building to second control joint OK from 12 to 16 feet. North, east, and south exterior walls OK from 16 to 20 feet.
04/09/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Ok to grout to 16’ on all 4 walls
04/05/2019 REINFORCED MASONRY PRE-GROUT Partial Approval West exterior wall at lentels (0’ to 2’-8" above lentel bottom) ok to grout
04/04/2019 REINFORCED MASONRY PRE-GROUT Partial Approval 3rd lift for North, West and South walls.
03/27/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Ok to grout first lift
(changed to PA due to more inpections needed)
03/11/2019 REINFORCED MASONRY PRE-GROUT Partial Approval Building stem ok to grout.