Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2019 | ELECTRIC - CONSTRUCTION POWER | Approved | ||
| 02/28/2019 | ELECTRIC - CONSTRUCTION POWER | Denied | #1: need to secure gas bond to house #2: need 1 more bracket on electrical panel riser below the roof line #3: need to bond water main #4: lock panel out until electrical is trimmed out |