Permit: T18CM08756

Parcel: 117030960


Addresses:

26 E 2ND ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T18CM08756

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2018 PLUMBING - FINAL Approved Clear gas meter
Verbal clearance called in at 8:25am
11/19/2018 PLUMBING - FINAL Denied 1- Shall seal the exterior gas penetration at rear of house.
2- Shall provide (3) sheet metal screws per joint on the water heater vent connector and draft collar.
3- Shall provide a water heater drip pan and terminate the T & P drain into the pan.
4 - Shall provide the approved plan and permit on site at time of inspection request.
5- Shall provide a carbon monoxcide detector and locate near the water heater