Permit: T18CM08693

Parcel: 12317148A

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T18CM08693

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2019 PLUMBING - ABOVE CEILING Approved
03/28/2019 PLUMBING - ABOVE CEILING Partial Approval Units in need of corrections; unit 3112 back pitch in bathroom to garage vent, double top plate cut too wide on first floor, engineering fix required. Unit number 3111, double top plate cut two wide engineering fix required.
03/26/2019 PLUMBING - ABOVE CEILING Cancelled Cancel by contractor
03/22/2019 PLUMBING - ABOVE CEILING Denied 1- Shall provide shield plates on all plumbing waste and vent lines that are within a 11/2” from the edge of plates.
2- Shall install the combination tee wyes horizontally to the 3 inch soil lines for the shower trap arms.
3- Shall provide a block or strap on all horizontal waste and vent line every 5 feet.
4 - Re test the DWV system.
03/21/2019 PLUMBING - ABOVE CEILING Not ready for Inspection cancel by contractor
03/19/2019 PLUMBING - ABOVE CEILING Cancelled Cancel by contractor