Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2019 | FIRE SPKLR - FINAL | Approved | ||
| 05/10/2019 | FIRE SPKLR - FINAL | Partial Approval | Still need to replace painted sprinkler upright head in corner front room. Replace painted head in bathroom and clean dust or paint in other bathroom. Rooms 123, 133, 129 and janitor closet push heads so they are recessed and holes are not exposed. Okay for TCO to move stuff in but not for occupancy. Re-inspection fee added. |
|
| 05/08/2019 | FIRE SPKLR - FINAL | Denied | 1. Replace painted upright sprinkler head in corner room. |