Permit: T18CM08481

Parcel: 116022760

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T18CM08481

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2019 BUILDING - FINAL Approved
05/01/2019 BUILDING - FINAL Partial Approval firecode clearances and panel layout not per drawing. Either revise drawings or move panels per plan. Also firecode clearances require 36 inches of width that are walkable, turbine roof vents may also need to be addressed as that makes the space un-walkable. Equipment OK.