Permit: T18CM08435

Parcel: 116180740


Addresses:

1252 W FRANKLIN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/27/2019 ELECTRIC - FINAL Approved
02/26/2019 ELECTRIC - FINAL Denied No disconnect/lock out for water heater, electric panel not labeled, no receptacles on island, two small appliance circuits required on kitchen counter.
01/04/2019 ELECTRIC - FINAL Partial Approval Submit as built to Riser diagram to show all in 1 panel with overhead in lieu of underground. Approved diagram does not match install. All overhead drops in area. 2065 not on inspection card, new service on plans. OK TO CLEAR SERVICE INC