Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2018 | ELECTRIC - SERVICE UPGRADE | Approved | TEP INCR | |
| 12/05/2018 | ELECTRIC - SERVICE UPGRADE | Correction Required | Install water bond Install TEP metal address label Label circuits If home has gas piping then bond pipe same as water using #4 copper for bonding Ground rods, weather head, riser and bracing are fine. OK to use existing gas and water bond if tied back into new panel and wire size is #4 copper. |