Permit: T18CM08371

Parcel: 135102660

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/10/2018 ELECTRIC - SERVICE UPGRADE Approved TEP INCR
12/05/2018 ELECTRIC - SERVICE UPGRADE Correction Required Install water bond
Install TEP metal address label
Label circuits
If home has gas piping then bond pipe same as water using #4 copper for bonding
Ground rods, weather head, riser and bracing are fine. OK to use existing gas and water bond if tied back into new panel and wire size is #4 copper.