Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T18CM08350
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2020 | FIRE - FINAL | Approved | ||
| 09/16/2019 | FIRE - FINAL | Partial Approval | -Install address on building -Post occupant load limit sign in lobby -Mount class K fire extinguisher in kitchen area -Provide and mount one- ABC fire extinguisher, minimum size 2A-10BC at a maximum travel distance of 75 feet. -Operational permit required for Places of Assembly through the Tucson Fire Department. (Application left on site) |