Permit: T18CM08158

Parcel: 134261980


Addresses:

1002 S KOLB RD #17

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/02/2019 MECHANICAL - FINAL Approved
02/21/2019 MECHANICAL - FINAL Not ready for Inspection Closet locked, no access
Spoke to contractors office and stated I would arrive after 2 stops. She said fine and thank you.
02/05/2019 MECHANICAL - FINAL Denied 1. Need secondary condensate line or automatic shut off.
2. Need drip leg on gas line.
3. Need supported air gap between condensate drain and sewer drain, or run into exterior.
4. Finish insulating HVAC lines in closet.
5. U-V Protect exterior HVAC lines tape.
6. Unit maximum fuse is 30 A. Presently it is 40 A.
7. Install tamper proof caps.