Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - LCEL - Electrical Underground |
|
Canceled |
Inspection Canceled |
| 04/21/2020 |
COT - LCEL - Electrical Underground |
WGALLAGHER |
Partial Approval |
Entered by RSALDAT1 - Partial approval #1,2,and 3 stilling pump risers ok for concrete placement
and pull box inclosures
Partial approval ok to backfill electrical conduit trenches for control room
|
| 03/04/2020 |
COT - LCEL - Electrical Underground |
DMUNIZ |
Partial Approval |
Entered by SFLORES2 - Added five Conduits to well 1,2,3... and four Conduits to gate. |
| 02/25/2020 |
COT - LCEL - Electrical Underground |
DMUNIZ |
Partial Approval |
Entered by DMERANZ1 - Electrical Conduits for Line voltage and low voltage from first pull box to second pull box and beyond. Progress ok to to shade, tape, and backfill. |
| 02/20/2020 |
COT - LCEL - Electrical Underground |
DMUNIZ |
Partial Approval |
Entered by DMERANZ1 - No inspection done today. Construction meeting with Clayton with Border land on method of installation for Conduits for wells and cameras. Ok to proceed & will intermittently call inspections while progress is made. |