Permit: T18CM08113

Parcel: 135074450

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T18CM08113

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2018 FIRE - FINAL Approved 12/27/2018
11/29/2018 FIRE - FINAL Partial Approval OK FOR TCO FOR FULL OCCUPANCY (SENT TO RECORDS)
11/29/2018 FIRE - FINAL Partial Approval APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY

Outstanding items for final:
1) Mount knox box next to riser door. Provide keys.
2) Mount sign "riser room" to door.
3) Mount sign "FACP" to door.
4) Post OL sign in A3
5) Will move/install 2 exit signs as discussed in A3.
Mike Floyd
603-1748
11/28/2018 FIRE - FINAL Cancelled Fees need to be paid by cutler before an inspection is scheduled. If inspector goes out prior additional fees will be added.
11/19/2018 FIRE - FINAL Partial Approval -Install panic hardware on existing doors per plans.
-install all fixed seating prior to the fire final.
-install all ceiling tiles.
-need annual sprink inspection report. deficiencies resolved.
-need 5yr internal check valve inspection and report.
-order knox box, install next to riser room, provide key.
-I will verify sprinkler monitoring requirment. appears it was monitored at some point.
-need to close out cutlers permit. they still owe fees.
-obtain operational permit for "places of assembly."