Permit: T18CM07732

Parcel: 130054720


Addresses:

2567 E MENOR SV

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/28/2018 EXT METAL CLIPS/EXT SHEATHING Approved
11/21/2018 EXT METAL CLIPS/EXT SHEATHING Partial Approval Provide hold-down Southeast corner
to 2 each ab's at brace panels
11/20/2018 EXT METAL CLIPS/EXT SHEATHING Denied 1-Provide listing for soffit boards to verify their use as roof sheathing.
2-Provide installation instructions for siding (not the T-111 shown on approved plans) to verify nailing requirements for use as braced wall panels and lack of moisture barrier in this installation.
3-Provide approved truss drawings.
4-Living Room header is undersized.
5-Install base plate anchors per Code.