Permit: T18CM07690

Parcel: 130111970

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/27/2018 PLUMBING - ROUGH, SOIL Approved
12/12/2018 PLUMBING - ROUGH, SOIL Correction Required Install green tracer wire at all drainage outside the building footprint.
I see washing machine plumbing added and not on plan and I do not see lavatory plumbing that is on the plan?
Install a double combine as a two way cleanout where you have installed the one way clean out.
Recommend a cleanout on the branch. Line serving the washing machine line.