Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2019 | ELECTRIC - FINAL | Approved | ||
| 05/28/2019 | ELECTRIC - FINAL | Denied | 1- Shall provide access to the roof at the time of inspection request. 2- Shall provide water hammer arrestors for the clothes washer. 3- Shall secure the floppy flex at the water heater disconnect in the basement and the liquid tight whips to the AC and split unit condenser on roof. |