Permit: T18CM07392

Parcel: 12009031B


Addresses:

214 E AVIATION DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/20/2018 ELECTRIC - FINAL Approved OK to clear solar DGC
12/14/2018 ELECTRIC - FINAL Partial Approval drawings (e-602.00 page 7) show a 200 amp panel only 100 amp panel installed. Drawings show Se-5000h inverter, SE-3800 is what is installed. Drawings show a 30 amp breaker that is not what is installed. Need to revise drawings or have the revision on site at time of inspection.