Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2019 | BUILDING - FINAL | Approved | ||
| 06/28/2019 | BUILDING - FINAL | Partial Approval | ending other inspections. | |
| 06/18/2019 | BUILDING - FINAL | Partial Approval | Pending other inspections | |
| 06/14/2019 | BUILDING - FINAL | Denied | 1- Shall provide a vacuum relief valve on the bottom fed water heater supply line. 2- Shall lower the accessible lavatories at 34 inches AFF. 3- Shall lower the grab bars no higher than 36 inches from finish floor to the top of grab bar. 4- Shall locate grab bars and all toilet accessories as per the approved restroom elevation detail. 5- Shall provide a accessible service counter 34 inches AFF. |