Permit: T18CM07360

Parcel: 129011100


Addresses:

2101 E BEVERLY DR

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/26/2019 FIRE - FINAL Approved
10/03/2019 FIRE - FINAL Partial Approval OK for TCO in office area.

Warehouse area still to be inspected
-exit signs & EM lights
-FDC sign
-HMIS
-Specifications for rack storage

Re-inspection fees incurred from this inspection forward
08/29/2019 FIRE - FINAL Partial Approval OK FOR TCO FOR MILL/CRUSHER AREA
REMAINING AREAS: EXIT SIGNS, EMERGENCY LIGHTING, FACP FDC SIGNAGE, KNOX FDC PLUG AND KEY BOX, ADDRESS NUMBERS ON BUILDING, PROVIDE HMIS ( HAZARDOUS MATERIAL INVENTORY STATEMENT)
08/26/2019 FIRE - FINAL Partial Approval -Install exit signs
-Install emergency lighting
-Provide and mount fire extinguishers
-complete electrical panel schedules
-Install signage "FACP" + "FDC"
-provide knox FDC plugs and knox key box
-Install address numbers on building